PN class |
PN 25 as per EN 1333
|
Permissible operating pressure |
2.500 kPa (25 bar) as per ISO 7628 / EN 1333
|
Max. differential pressure |
600 kPa
|
Min. differential pressure |
See tables volumetric flow/dial presetting
|
Valve characteristic |
Linear as per VDI/VDE 2173
|
Leakage rate in general |
Class IV (0…0.01% of volumetric flow V100) to EN 1349
DN 25…32 with STA..3..
Class III (0…0,1% of volumetric flow V100) per EN 1349
|
Average flow accuracy |
+/-10% from ΔPmin – to 2.5 x ΔPmin
+/- 5% from 2.5 x ΔPmin – to 600kPa
|
Permissible media |
Low-temperature hot water, chilled water, water with antifreeze
Recommendation: Water treatment to VDI 2035
|
Medium temperature |
Valve with actuator 1…120 °C
Valve with actuator 1…110°C with SUA21/33), SUA21/3P, SUE21P
|
Permissible ambient temperature |
1…50 °C
|
Materials |
Valve body, port, seat, sealing gland and test points: Dezincification resistant hot-pressed brass (DZR), CW602N
Valve body DN 40…50: Nodular cast iron
|
Stem, spring |
Stainless steel
|
Presetting element |
PTFE, PPO, POM C and ABS
|
Regulator |
PPS
|
Seals |
EPDM 281 (O-ring)
|
Threaded connections |
VPP46..: G to ISO 228-1 (externally threaded)
VPI46..: Rp to ISO 7-1 (internally threaded)
|
Actuator connection |
DN 10…32: M30 x 1.5 mm
DN 40…50: Siemens large stroke connector
|
Pressure test points (P/T-ports) |
G 1/4” (connection valve body)
2 mm x 40 mm (needles)
|