Applications
- 2-pipe fan coil units, 2-pipe with electric heater, 2-pipe with radiator/floor heating
- 4-pipe fan coil units, 4-pipe with electric heater
- 2-stage heating or cooling application
- Compressors in dx-type equipment
- Universal heating and/or cooling
Features
- 2 multifunctional inputs and 1 digital input for keycard contact, external sensor, etc.
- Operating modes: Comfort, Economy and Protection
- Automatic or manual heating/cooling changeover
- Adjustable commissioning and control parameters
- Minimum and maximum setpoint limitation
- Backlit LCD
- Selection of fan stage in the dead zone via P15
Functions
- Maintenance of room temperature via built-in temperature sensor or external room temperature/return air temperature sensor
- Automatic or manual changeover between heating and cooling mode
- Selection of applications via DIP switches
- Selection of operating mode via the operating mode button on the thermostat
- 1-speed, 3-speed or DC…10 V fan control (automatic or manual)
- Display of current room temperature or setpoint in °C and/or °F
- Minimum and maximum setpoint limitation
- Button lock (automatic or manual)
- 1 digital input, freely selectable for:
– Operating mode switchover contact (keycard)
– Automatic heating/cooling changeover contact
– Electric heater enable
– Dewpoint sensor
– Fault input - 2 multifunctional inputs, freely selectable for:
– Operating mode switchover contact (keycard)
– Automatic heating/cooling changeover sensor
– External room temperature or return air temperature
– Dewpoint sensor
– Electric heater enable
– Fault input
– Supply air temperature sensor (RDG160T..) - Advanced fan control function, i.e. fan kick, fan start, selectable fan operation(enable, disable or depending on heating or cooling mode)
- Purge function together with 2-port valve in a 2-pipe changeover system
- Reminder to clean filters
- Floor heating temperature limit
- Minimum and maximum supply air temperature limitation (RDG160T..)
- Reloading factory settings for commissioning and control parameters
- 7-day time program: 8 programmable timers to switch over between Comfort and Economy mode (RDG100T, RDG160T..)
- Infrared remote control (RDG100T, RDG160T..)
- Selectable relay function (RDG160T..)
– For switching OFF external equipment OFF during Protection mode
– For switching ON external equipment (e.g. pump) during H/C demand
– Output heating/cooling sequence - Wizard function to select working temperature unit °C or °F (RDG160TU, RDG110U)